SA380TX Configuration

To connect an Aster VTI21 to an SA380TX, Generic Logger firmware is required.

This is version 1.5G557 and is available from the MPEC website here: http://www.mpec.co.uk/downloads/Test_Releases/TX2%5b1.5G557-802%5d.zip

The unit can be upgraded to this version of firmware if required using dUpgrade, following the instructions found in the dUpgrade User Guide.

Contact MPEC for instructions on how to upgrade via USB.

Once the SA380TX is running the correct version of firmware, it must be configured to acquire data from the Aster VTI21 over 4-20mA and RS485 connections.

4-20mA Output:

This requires connection of the 4-20mA output to an analogue channel on the SA380TX. Please see VTI21 VTi21 Hardware Wiring for 4-20mA Operation and follow the instructions titled "Wiring for 4-20mA Operation".

To configure the analogue channel of the SA380TX to accept the 4-20mA output of the VTI21 VTi21 the web config tool should be used.

To do this, firstly connect to the SA380TX over ethernetEthernet, then open a preferred web browser and type [SA380TX IP]/config into the URL. This should open the web config tool.

...

Apply the suggested settings shown below to the analogue channel that is connected to the VTI21 VTi21 4-20mA output.


RS485:

For information on the wiring required for RS485 communications please see VTI21 VTi21 Hardware Wiring for 4-20mA RS485 Operation  and follow the instructions titled "Wiring for RS485 Operation" or "Alternate Wiring for RS485 Operation" dependant on the SA380TX's hardware configuration.

To configure the VTI21 VTi21 over RS485, please follow the instructions under the heading "Configuration on RS485" in the VTI21 VTi21 Configuration guide.

After configuring the RS485 connection, each reported channel needs to be assigned to an analogue channel using the settings shown below.

...

See the table in the Aster VTI21 VTi21 Outputs for the units and change threshold for each channel.

...

  • This feed must pass through the current transducer connected to the "CH1" input on the VTI21VTi21.


If monitoring of an additional Aster receiver is required, the feed connecting to REC. 1 of the second receiver must pass through the current transducer connected to the "CH2" input on the VTI21VTi21.

The 4-20mA output of the VTI21 VTi21 only reports current for CH1.

Note

Ensure that the current transducers used for Aster applications are correct. Although they have the same part number as the transducers used in other VTI21 VTi21 applications, the type required for Aster must state that they are 40K BURDEN.

See the image below for further clarification.

...

Please observe that as this is an AC application the device operation is unaffected by the direction that the wire is fed through the current transducer.


Aster

...

VTi21 Outputs

The Aster VTI21 VTi21 sensor can output the following quantities when monitoring Aster receivers.

  
QuantityUnitsChange Threshold4-20 mARS485
CH1_AsterHz1

 

  •   
CH1_ICentuA1050
  •   
  •   
CH1_FreqHz1
  •   
CH1_ITotuA1050
  •   
CH1_1700uA10 50
  •   
CH1_2000uA1050
  •   
CH1_2300uA1050
  •   
CH1_2600uA1050
  •   
CH1_FFT
Not normally acquired
  •   
CH2_AsterHz1
  •   
CH2_ICentuA1050
  •   
CH2_FreqHz1
  •   
CH2_ITotuA1050
  •   
CH2_1700uA1050
  •   
CH2_2000uA1050
  •   
CH2_2300uA1050
  •   
CH2_2600uA1050
  •   
CH2_FFT
Not normally acquired
  •   

...