- At present, the SA380-IT measures the degree of isolation between circuit circuits as a standing voltage between the two circuits being measured. A table (at the end of this document) must be utilised to determine the possible level of insulation resistance.
- Connecting both B12 and XB12 circuits in the standard arrangement adds the ability to monitor nominal circuit voltage and isolation from earth. This is important as a low nominal circuit voltage may mask an inter-circuit isolation fault due to lower than expected standing voltages.
|
...
Device misoperation is also possible due to cross-coupling of circuits that are where the fault path is not via an earth connection.
...
Use the look up table below to convert the voltage present on wither either the "ISO 1" or "ISO 2" channels into a worst-case level of inter-circuit isolation.
...