Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Info
  • At present, the SA380-IT measures the degree of isolation between circuit circuits as a standing voltage between the two circuits being measured. A table (at the end of this document) must be utilised to determine the possible level of insulation resistance.
  • Connecting both B12 and XB12 circuits in the standard arrangement adds the ability to monitor nominal circuit voltage and isolation from earth. This is important as a low nominal circuit voltage may mask an inter-circuit isolation fault due to lower than expected standing voltages.

...

Detectable Faults

...

Low Nominal Circuit Voltage

Monitoring the circuit voltage allows abnormally high, or abnormally low battery voltage to be detected. This is well documented in the existing user-guide.

  • Detect failing battery cells or chargers
  • Warning that inter-circuit isolation may be lower than suspected in the event of a low nominal voltage

Isolation from Earth

The SA380-IT is primarily designed to ensure supply circuit that are earth-free by design remain so, Connecting both B12 and XB12 in the normal arrangement ensures that this is true.

This is well documented in the existing user-guide.

Inter-Circuit Isolation

Device misoperation is also possible due to cross-coupling of circuits that are not via an earth connection.

By wiring SA380-IT inputs "cross-pole" between two circuits, a standing voltage on the SA380-IT inputs will be observed if any of the four fault conditions shown below are true.

The wiring diagram above shows this "cross-pole" arrangement on inputs 2 and 3.

Fault 1 and Fault 2 cause a voltage to present across both of the SA380-IT inputs. In this scenario the voltage may be as high as the nominal circuit voltage.

...

Alternatively Inputs 4 and 5 can be wired directly across the terminal of each circuit to provide remote cell voltage monitoring. A wiring diagram showing such a solution is shown below View filenameCP Typical Circuits-2.pdfheight250



Configuration


Fault Resistance Table

...