The logger monitors the RS485 bus of the IRDH575-EDS490 system.
RS485 settings: 9600 Baud 7E1
Simplest to configure on touch-screen:
Add a Bender slave unit:
Adding it by hand on the touch-screen creates configuration:
<ConfigRs485> <owner>bms</owner> <baud>9600</baud> <byteLen>7</byteLen> <stopBits>0</stopBits> <parity>2</parity> <frameSep>500</frameSep> <listenTout>1000</listenTout> </ConfigRs485> <slaveCfg> <slave id="0" ip="0.0.0.0" unique="00000000_00000000" type="bender" model="" manuf="0" /> </slaveCfg>
RS485 settings are actually used by the BMS module. Touch-screen configuration sets them, but hand-crafted XML must set them correctly.
Not all BMS units are equal: they can have (and do have!) different set of channels. Whenever connecting to a new installation: please remove the existing Bender slave unit from the configuration and insert it again!