Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 9 Next »

Technical specifications

General

Digital inputs per unit

4, 12 or 20

Analogue inputs per unit

2, 6 or 10

Fixings

To fit standard BR930 relay rack

Size

135 x 57 x 175mm - 1 relay position

Processor

80MHz dual

RAM

256K

Internal flash storage

2GB

 

Communication ports

Ethernet10baseT

Internal modem

GSM/GPRS

RS485

 

Protocols

PPP, TCP/IP, HTTP,  FTP,  MIMOSA, RailDAQ

 

Digital input ports

Type

Volt-free relay contacts
Isolation Barrier10MOhm at 1,000V DC min
Max differential DC voltage55V

 

Analogue input ports

Range4-20mA
Resolution10 bit
Sampling rate1000 Hz Max.
Isolation Barrier10MOhm at 1,000V DC min

 

Power supply ports

Power supply

90-264Vac
Isolation Barrier10MOhm at 1,000V DC min
Power consumption no inputs3W
Power consumption absolute max40W (0.36A at 110V)

 


MIMOSA parameter offsets

Main Offsets

OffsetTypeMeaning
0-Base ID of logger
1

DABLOBData

SNTP time server domain name
2DABLOBDataFTP Server domain name
3DABLOBDataPrimary server domain name
4DABLOBDataSecondary server domain name

5

DABoolHeartbeat

6

DAInt

Heartbeat interval
7DABLOBData

FTP download request

8DABLOBDataFTP download report

9

DABLOBData

Firmware update request

10-31

-

Reserved

32

DABool

System reset

34DABoolRestart comms
64-75

DAWaveform

Triggered captures 1-12 recorded waveforms

128-147DABool

Digital inputs

576-585DADataSeq

Analogue inputs 1-10 using Acquire-on-Change

1024-1035

DAInt

Triggered captures 1-12 direction indicators

   
   
   
   
   
   
   
   


 

 

 

 

 

  • No labels