Introduction

Can monitor 1 x Bender unit Type IRDH265

other benders may be supported - check the Bender documentation to see if the RS485 protocol matches

1 x TX can only monitor 1 x Bender. This is a limitation of the protocol, not the SA380TX.


Data Available

Instantaneous Resistance to Earth

Present Alert Levels

Fault Repeat Relay Status

Alarm Status

Connection Error

AC Fault

DC+ Fault

DC- Fault

Fault Repeater Output


Wiring

RS485

typical rs485 stuff


4-20mA

Not recomended, but could be employed to connect multiple bender units to a single TX by utilising spare analogue inputs.

Be aware that the reading will be prone to error due to the strange equiation used by the 4-20mA signal converter:

R equation

This has to be approximated on an SA380TX using the following equation:

TX equation

ERROR PLOT

The set-up of this is described below


Digtial

Where a fault repeater exists, up to 12 digital outputs may be provided to indicate which sub-feeder is experiencing the worst insulation resistance. These are wired as per standard digital inputs


Configuration & Comissioning

Setting up the Channels


Rs485

Set the RS485 owner to "Bender"

TOUCHSCREEN - CONFIG TOOL

Create a "Bender" slave unit

TOUCHSCREEN - CONFIG TOOL

This will "Create" slave analogue and digital channels

WEB CONFIG OF CHANNELS

Check that device is active:

MAIN SCREEN

REALTIME DIGITAL

REALTIME ANALOGUE

4-20 mA

Wire the input circuit as a "loop powered" 4-20mA input as shown below

4-20MA CONNECTION

You will need to apply a polynomial mapping to translate the 4-20mA output into a resistance

Please ensure you enter the values below EXACTLY

This curve fit is designed to minimise error below 150 k Ohm

Digital

Simply Rename the Digital Channels to match the feeder same (e.g UP, DOWN, BRANCH etc)


Setting the Acquisition

This requires connection via laptop

The touchscreen interface is not sophisticated enough to set this up

Alarm Levels

Use a simple acquire on Change:

TOUCHSCREEN - CONFIG TOOL


Digital Channels

Simply select push-to-server for all physical and RS485 channels

Live Insualtion Resistance

Standard acquire-on-change will grab incoming data based on on absolute change.

This is not desirable when taking insulation resistance readings, as an absolute change of 10 k Ohm from 1 M Ohm to 990 k Ohm will happen very frequently, due to wet weather for instance, and not warrant any corrective actions, where a change from 55 k Ohm to 45 k Ohm would cross an alert boundary and warrant immediate corrective action.

Setting a small threshold will cause a large amount of not very useful data to be captured, whereas setting a large threshold would cause low data volumes, but reduce sensitivity to genuine fault conditions.

To counter this, the "relative" acquire on change must be set on the logger. To do this requires the use of the "Rail Event" feature of the SA380TX

CREATE NEW RAIL EVENT

SET START TRIGGER
SET ACQUISITION

SET END TRIGGER

Set the config