- Set acquire-on-change on analogue channel 2, enable it, push data to the central system, acquire whenever the value changes by 2.5% of full scale, package acquired samples if there are no more samples acquired after 2 seconds or if there are 100 acquired samples waiting to be sent.
Note |
---|
Note that: Acquire-on-change works on a percentage of full scale deflection. Hence if the full scale of the input is 600mA, 2.5% of this is 15mA, and so the logger will acquire a sample if the input changes by more than 15mA. |
...
SetCfgResponse
The response from the logger to both the captures and acquire-on-change messages is as follows:
...