Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

The detailed set-up of the 4-20mA is described below

...

Digital Volt-Free-Contact Interface

Where a fault repeater exists, up to 12 digital outputs may be provided to indicate which sub-feeder is experiencing the worst insulation resistance. These are wired as per standard digital inputs:

...

Info

The diagram on the left shows direct connection. Please consult the Bender user guide for exact terminations.

Note that if the isometer is built into a Network Rail style cubicle arrangement, the "common" VFC connection is brought-out at the base of the cubicle through the terminal block position 37. The 12 individual feeder alarm signals are presented on terminal 38 (Feeder 1) through to 49 (Feeder 12). This is shown on the right

...

Channel Configuration & Commissioning

Info

Always remember to set the config on the SA380TX before closing the web-page, or touch-screen dialog box! Your changes won't take effect otherwise!

Initial Setup

RS485 Setup

These steps may be completed on the SA380TX touchscreen, or via web-based configuration tool.

1) Set the RS485 "owner" to "Bender". This tells the SA380TX what type of device is attached to the RS485 port

TOUCHSCREEN - CONFIG TOOLMenu→Configuration→RS485

Image Added

Image Added


2) Create a "Bender" slave unit. The SA380TX needs to be explicitly told about devices attached to the RS485 port. Remember, only a single isometer may be connected at any one time.

TOUCHSCREEN - CONFIG TOOLMenu→Configuration→TX Slaves

Image AddedImage Added

Image Added

3 ) Check that the "Slave" has been successfully created

The SA380TX will create additional slave channels representing the data obtained over the RS485 interface. The screen grab below shows these channels in the web-based configuration tool. They will also be visible in the real-time displays and historic data logs accessible via the touch-screen,

WEB CONFIG OF CHANNELSImage Added

4) Check that the isometer device is active:

...

Additional alarm state changes may also be observed, but not if no fault condition exists.

Image Added

Real Time Digital Screen:

...

This screen is a poor indicator of connection status, as the state of the digital channels depends on the fault condition of the cables under test. Bender CONN DN should be clear.

Image Added

Real Time Analogue Screen:

...

This should show the present alarm levels, as well as the current resistance to earth reading obtained from the isometer. The value of the Bender Insulation channel must match the value displayed on the isometer display exactly.

Image Added


Info
titleTrouble Shooting

If no RS485 data is visible:

  • Be patient. isometers may take up to 2 minutes to complete a single measurement, therefore it may be up to two minutes before data is visible
  • Check the integrity of the wiring. It could be poorly terminated cable.
  • Check the polarity of the wiring. It is very easy to get the "A" and "B" the wrong way around
  • Check for data on the RS485 bus. Ideally use a serial port on a computer to check for traffic. The baud rate is 9,600 bps. You should a string of numbers being transmitted periodically
  • Check for data on the RS485 bus. Alternatively connect a volt-meter with a rapid response across the A and B links. a brief spike in voltage should be observed when data is present on the bus,  Bear in mind the low update rate, and that the RS485 message only lasts a few milliseconds.



4-20mA Setup

You will need to apply a polynomial mapping to translate the 4-20mA output from the Bender RK170 into a readable resistance.

...

COMING SOON - REAL-TIME ANALOGUE DATA


Digital

...

Setup

You will need to name any digital channels that derive from the fault evaluator unit.

Simply click on the "name" field in the web-based configuration tool to rename the digital channels such that they match the feeder name (e.g UP, DOWN, BRANCH etc)

Setting the Acquisition

This requires connection via laptop

Image Added

...

Acquiring and Transmitting Data


Info

To perform the steps described in this section requires the use of the web-based configuration tool.

The touchscreen interface is not sophisticated enough

...

.

Analogue Alarm Levels

Use a simple absolute acquire on Change:

TOUCHSCREEN - CONFIG TOOL

. Double-Click on each of the Bender ALARM1 and Bender ALARM2 channels in turn and enter the setting shown below:


Image Added



All Digital Channels

Simply select push-to-server for all physical and RS485 channelsLive Insualtion Resistance. This is achieved by ensuring the "Push to Server" tick-box is checked for digital channels you which to send to Centrix, as shown below

Image Added


Live Insulation Resistance (4-20 mA or RS485)

Standard acquire-on-change will grab incoming data based on on absolute change. This is not desirable when taking insulation resistance readings, as an absolute change of 10 k Ohm from 1 M Ohm to 990 k Ohm will happen very frequently, due to wet weather for instance, and not warrant any corrective actions, where . Whereas a change from 55 k Ohm to 45 k Ohm would cross an alert boundary and warrant immediate corrective action.

Setting a small acquisition threshold will cause a large amount of not very useful data to be captured, whereas setting a large threshold would cause low data volumes, but reduce sensitivity to genuine fault conditions.

To counter this, the "relative" acquire on change method must be set on the logger. To do this requires the use of the "Rail Event" feature of the SA380TX

CREATE NEW RAIL EVENT

SET START TRIGGER
SET ACQUISITION

SET END TRIGGER

Set the config.

1) Open the "Rail Events" Tab - This is where we can create all sorts of clever acquisition rules.


Image Added

2) Create a new "Rail Event" - This sets up a new set of acquisition rules. It is OK for your Rail Event to errors at this stage.

Image Added

3) Create the "Start Trigger" - We want to acquire data when the SA380TX boots up, and then whenever there is a significant change in insulation resistance. Whenever there is a +/-5% change in insulation resistance, a new acquisition is started. It is OK for your Rail Event to errors at this stage.

Image Added

4) Tell the SA380TX what to Acquire - We want to keep acquiring insulation resistance values so long as they continue change. Every time the insulation resistance changes by another 5% of its prior value, we grab another sample. It is OK for your Rail Event to errors at this stage.

Image Added

5) Set the end conditions - We don't need an "end trigger" we keep on acquiring samples so long as they continue to change. At some point though we want to barrel these samples up and send them to Centrix. This is why we put a time-out period of 1 minute in place.

After 1 minute acquisition will end, and all samples acquired since the start trigger event will be sent to Centrix. Don't worry though, next time Insulation resistance changes by 5%, a brand-new acquisition will be triggered and the whole process repeats.

Your Rail Event should now have no errors.


Image Added


Info

Always remember to set the config on the SA380TX before closing the web-page!