Overview

Introduction

...

  • The SA380TX can monitor 1 x Bender

...

  • type IRDH265 / 365 insulation monitor.
  • In addition to the isometer, volt-free contact outputs from Bender fault-repeater devices (such as the ESD-470) may also be connected the SA380TX general purpose digital inputs.
  • If a 4-20mA output converters such as the RK170 is utilised, this can be connected to the SA380TX general purpose analogue inputs, although RS485 connection is preferred.
  • Other models of Bender isometer may be supported over RS485 - check the Bender documentation to see if the RS485 protocol matches
  • Please be aware that 1 x

...

  • SA380TX can only monitor 1 x Bender Isometer. This is a limitation of the Bender protocol, not the SA380TX.

Data Available

ParameterUnitsRS4854-20mADigital VFCNotes
Instantaneous Resistance to Earth

Present Alert Levels

k Ohm
  •  
  •  

This is the last reading of Resistance-to-Earth taken by the isometer
Alert Levelsk Ohm
  •  


The isometer permits two configurable alert thresholds. These levels are both reported
Alarm StatusDigital
  •  


Reports if either alarm level has been breached
Fault Repeat Relay Status

...

Digital
  •  


Reports if output fault relay has been energised. Essentially mirrors alarm status
Connection ErrorDigital
  •  

AC Fault

DC+ Fault

DC- Fault

...



Set to UP or TRUE is not RS485 data has been received from the isometer for 7 minutes.
AC, DC+, DC- FaultDigital
  •  


For DC Systems, Indicates which leg is experiencing the worst fault. For AC systems, only the AC flag will be asserted.
Fault Repeater OutputDigital

  •  
Where a fault repeater is provided and a single isometer monitors a multiple-feeder arrangement, a digital volt-free-contact output is provided for each feeder. The feeder experiencing the worst fault will have its contact closed.

These parameters can be continuously monitored to perform long-term trend analysis of cable condition, to alert maintainers of faults that require intervention, and to aid diagnosis of the fault type and location.


Wiring

RS485

typical rs485 stuff

...