Since 4.9.5 the protocol between SA380 master and SA380 slave units has been changed. The new protocol needs some extra configuration.

Step-by-step guide

Setting up SA380 master unit:

  1. Set local IP address. (The slave units will be needed to be configured to connect to this IP address.)

    Image Added
    Press Menu:
    Image Added
    Press Configuration and enter passcode:
    Image Added
    Press Set local IP:
    Image Added
    Enter appropriate master IP address, subnet mask and default gateway. The default – and most usual – settings are:
    IP address: 10.0.1.1
    Subnet mask: 255.255.252.0
    Default gateway: 10.0.0.138
    Press Enter when finished.
  2. Enter each slave unit's serial number to tell the master unit what slave data to anticipate.

Setting up SA380 slave unit:

  1. Set local IP address. The slave must be able to connect to the master unit. There is no special restriction on the slave unit's IP address.
  2. Enter the master SA380 logger's IP address to make the slave unit to connect to the master.

Once the master and slave units are both configured, the communication can be verified:

 