Editing Acquire on Change & Digital Acquisition in XML on Generic Logger
The following changes are made using the SA380TX_Modstate_3_Generic_Config_Tool_v3_02. Clicking the link will allow you to download the config tool from the mpec website.
Enter the IP address of your logger into the "Logger Address" box
Click "Get Config"
To Edit Acquire on Change Settings
In all cases, the simplest way to locate a section of config is to use the "find" function (Ctrl+F)
Use Ctrl+F and search for "acqChgs"
Typically, you will want to change the "Acquire on Change threshold". To do so, edit the number next to "chg"
To change the Acquire on Change below from 5 to 50, simply enter chg="50".
The units are the same ones used by the sensor attached to the channel, so if "channel id 0" is set to read signals in volts, chg="50" means record changes of 50 volts or more
The "id" field in the above config relates to a particular analogue input.
The analogue inputs can be seen in the <anaIn> section of the config (shown below)
acquire on change id="0" therefore relates to analogue input AN-A01 (Note how uid of the input matches the id of the acquire on change)
acquire on change id="1" therefore relates to analogue input AN-A02
To Edit Digital Settings
Typically, you will want to "push" digital channels to a server.
Add a line to the config for every digital channel you wish to push
The config below will push channels with id 1 to 4 to the server
Please be aware! digital channels start at 0. id=0" means digital input channel 1, id="1" means digital input channel 2.
The "id" field in the above config relates to a particular digital input.
The digital inputs can be seen in the <digIn> section of the config (shown below)
dip id="1" therefore relates to digital input "Relay A-02" (Note how uid of the input matches the id of the dip)
dip id="2" therefore relates to digital input "Relay A-03"
j