How to push digital channel data to server using web configuration tool or the raw XML confuguration.
When you have direct access to the logger:
Enter the logger’s IP address into your browser eg. http://10.0.1.1/config
Navigate to Real Channels
3. Click on the tick-box in Push to Server column.
4. Click Set Config on Logger to send all the configuration changes back to the logger.
When logger is connected to Centrix and able to retrieve the XML configuration:
Visit the logger in centrix.org
Go to the READ/WRITE CONFIG tab
Press Read Device Config to retrieve the latest configuration from the logger
Click on Open As XML
Scroll down until you find the <ConfigDip> part
Add the channels you wish to be pushed to server by their ID:
<dip id="384" push="1" /> |
7. Click Write Device Config to send the changes back to the logger.
Channel numbering: id=0 to 26 belong to the master logger id=384 to 767 belong to the first slave unit id=768 to 1151 belong to the second id=1152 to 1535 to the third id=1536 to 1921 to the fourth id=1922 to 2305 to the fifth id=2306 to 2689 to the sixth id=2690 to 3074 to the seventh slave unit |
Let’s say you want to push the second channel on the first slave unit:
Channel ID = 384+1
In the XML configuration:
<digIn> <uid>385</uid> <name>TXL1-Relay 02</name> <invert>false</invert> <debounce>40</debounce> </digIn> |
uid=384, the same id is needed in the DipCfg:
<ConfigDip> <dip id="0" push="1" off="128"/> <dip id="1" push="1" off="129"/> <dip id="2" push="1" off="130"/> <dip id="3" push="1" off="131"/> <dip id="4" push="1" off="132"/> <dip id="5" push="1" off="133"/> <dip id="6" push="1" off="134"/> <dip id="7" push="1" off="135"/> <dip id="8" push="1" off="136"/> <dip id="9" push="1" off="137"/> <dip id="385" push="1" /> </ConfigDip> |