This should show the present alarm levels, as well as the current resistance to earth reading obtained from the isometer. The value of the Bender Insulation channel must match the value displayed on the isometer display exactly.

Image Added


Info
titleTrouble Shooting

If no RS485 data is visible:

  • Be patient. isometers may take up to 2 minutes to complete a single measurement, therefore it may be up to two minutes before data is visible
  • Check the integrity of the wiring. It could be poorly terminated cable.
  • Check the polarity of the wiring. It is very easy to get the "A" and "B" the wrong way around
  • Check for data on the RS485 bus. Ideally use a serial port on a computer to check for traffic. The baud rate is 9,600 bps. You should a string of numbers being transmitted periodically
  • Check for data on the RS485 bus. Alternatively connect a volt-meter with a rapid response across the A and B links. a brief spike in voltage should be observed when data is present on the bus,  Bear in mind the low update rate, and that the RS485 message only lasts a few milliseconds.

...

Acquiring and Transmitting Data

...


Info

To perform the steps described in this section requires the use of the web-based configuration tool.

The touchscreen interface is not sophisticated enough.

...