  • Antenna and antenna cable are supplied separately.

  • Mount the antenna external to the building

  • Never mount antenna inside an equipment enclosure or building

  • The antenna must be placed a minimum of 3 meters from sensitive electronic signalling equipment such as SSI.

  • The antenna features a magnetic mounting base. If this is not suitable, contact MPEC to discuss alternate mounting arrangements.

  • The antenna is to be mounted upright, with the “whip” element pointing skyward.

  • Ideally the antenna shall be placed clear of large structures and earthworks.

  • Bear in mind during placement that the antenna may need relocating during commissioning if inadequate signal strength is available.

  • A minimum12 mm circular aperture is required to route the antenna cable into the building / enclosure.

  • If the building or enclosure structure must be pierced to run the antenna cable, ensure this is done in a responsible manner using appropriate tools. Any new openings must be appropriately sealed against moisture ingress and rodent attack.

  • route the antenna cable using appropriate cable management from antenna to SLX device.

  • Avoid sharp radius bends and never bend the antenna cable tighter than a 13mm radius.

  • Avoid running the antenna cable directly parallel and close to sensitive digital signal cables, such as SSI data links.

  • Do not attempt to shorten or lengthen the cable unless competent to do so and in possession of the appropriate tools and connectors.

  • MPEC offer a range of antenna cable lengths, so please contact MPEC if the standard 5m cable is inappropriate.

  • Hand tighten the hexagonal SMA connector to terminal W1 of the S-LX compute module. Do not use tools to over-tighten.

  • Hand tighten the round TNC connector to the antenna base. Do not use tools to over-tighten.

Connect AC Power Supply

General

  • The HZS PSU and Port Isolator plug connector features six terminals:

    • 2 x BX terminals. The terminals are electrically common and accept the “live” connection to the incoming AC power supply.

    • 2 x NX terminals. The terminals are electrically common and accept the “neutral” connection to the incoming AC power supply.

    • 2 x E terminals. The terminals are electrically common and provide a protective earth connection to the incoming AC power supply.

    • The electrically common terminals allow power circuits to be daisy-chained to multiple S-LX systems whilst only occupying a single primary busbar connection.

  • Each terminal features a spring-cage contact to prevent accidental contact with hazardous live voltage. Guidelines for successful and safe connection are as follows

    • Maximum conductor area of cable should be 1.5 mm square

    • Cables shall always be fitted with ferrule crimps of the appropriate size.

    • Ferrule crimps shall be fitted using a “square end crimper”, such as WEIDMULLER PZ 10 SQR WIRE END FERULE CRIMPER. P/N: 1445080000

    • A tool is required to release the spring inside the connector to allow cable insertion

    • When fully inserted, no exposed conductor or ferrule should be visible to prevent electrical shorting and shock risk

Connection to BX110 Isolated Signalling Supply

  • The HZS device is product approved by Network Rail for connection to all 110 V AC isolated power circuits.

  • BX terminal shall be connected to a fused position on a BX110 busbar

  • The primary fuse shall be of 3 Amps - Slow Blow (3TA)

  • NX terminal shall be connected to a vacant position on a NX110 busbar

  • E terminal does not require terminating as a protective earth bond is not required, however, safety and performance is not compromised if the earth terminal is connected.

Connection to 230 V AC Domestic Supply

  • The HZS device has been safety tested for connection to 230 V AC domestic mains supplies

  • The HZS device remains isolated from earth unless under fault condition.

  • The BX terminal shall be connected to an appropriate “live” AC connection.

  • The primary fuse shall be of 3 Amps.

  • The NX terminal shall be connected to an appropriate “neutral” AC connection.

  • The E terminal must be connected to a suitable protective earth connection. This is required to provide electric shock protection under fault condition.

  • Protective Earth connection cable shall be of 1.5 mm square CSA.

Connect Serial, Ethernet or USB Connection

  • Connections to monitored signalling equipment are made through serial, Ethernet or USB ports

  • Refer to the example “overlay diagrams” which detail connection of the monitoring ports.

Note

Installation of monitoring connections can cause loss of system service in some applications.

Consult the individual application pages for more information.

If in doubt. Please contact MPEC for further guidance.

Commissioning

Energise Power Supply

...